Delta PLC Connect WinCC TIA Portal – How to communicate the Dela PLC and SCADA Software? This post 365electricalvn guides you to connect a Delta PLC with WinCC RT Advanced on TIA Portal through KEPServerEX 6
Delta PLC connect WinCC On TIA Portal – The Method To Connect
To connect Delta PLC with WinCC on TIA Portal we used:
- Delta PLC Connect WinCC on TIA Portal – Hardware used:
- Delta PLC Model DVP16ES2
- Delta DOP-100 HMI communication DVP PLC for monitoring and controlling the PLC values. And the Delta HMI is connected to the PC by using VNC Viewer. You can make the testing without HMI.
- USB-Serial Cable for downloading the PLC program and connecting the Delta PLC to KEPServer software.
- Delta PLC Connect WinCC – Software used:
You can download all software on 365EVN.
Could be helpful for you:
- Download PLC Program Using USB Through HMI Delta DOP-100
- S7-200 and WinCC Flexible. How to Make a Communication? Tutorial 1
- Learn S7-1200. Some Things You Need To Start A Project
The Steps To Connect WinCC RT Advanced With Delta PLC
Connect Delta PLC With KEPServerEX
Please refer to the previous post on 365EVN to create, and make a communication of the PLC Delta and KEPServerEX 6 use Modbus. We guided in detail.
Communication WinCC RT Advanced On TIA Portal and KEPServerEX 6
Follow the steps to connect WinCC and Kepserverex:
- Open TIA Portal and create a new project. And then “Add new device” -> “PC systems” -> “SIMATIC HMI application” -> “WinCC RT Advanced”.
- On the project, tree select your device (HMI RT [WinCC RT Advanced]) click “Connection” and add a new connection. Enter the name and select the communication driver as “OPC”. On the “Parameter” tab -> “OPC Server” -> “Local Server” select “Kepware.KEPServerEX.V6”.
- On the project tree select your device (HMI RT [WinCC RT Advanced]) click “HMI tags” -> “Add new tag table” and then “Add new”. Select the connection we added in the previous step. With “Address” we select the tags from KepServerEX V6.
- Click “Screens” -> “Add new screen” and then create the objects as normal with the address from the HMI tag table.
- Click “Runtion on the PC” to check the connection between PLC Delta and WinCC RT Advanced.
Guide Video To Connect Delta PLC With WinCC RT Advanced
If you can not watch the video above, please check another link in my Video Area (V0044) or give feedback to me via WhatsApp, Email, or Message. Thank you!
- All guide videos about PLC HMI, VFD and Servo programming by 365evn (Video area): Link
Link To Download The Source Files
- Link Download Project source files WinCC RT Advanced (TIA Portal V15.1): Link
- Delta PLC, HMI Program and KEPServerEX files: Link
If you have any questions about: “Delta PLC Connect WinCC on TIA Portal Through KEPServerEX 6” please comment below.
See you in the next posts!
-By 365electricalvn-