Simatic KTP700 Basic HMI and S7-200 PLC Communication Use RS485 Interface

s7 200 ktp700 basic dp communication

How to communicate Simatic KTP700 Basic DP HMI and S7-200 PLC using RS485 Interface? This post guides you to do it.

Communication KTP700 Basic HMI and S7-200 PLC. What do you need?

To connect KTP700 Basic HMI and S7-200 PLC you need some things:

  • The Software:
      • For HMI device: WinCC V13 or higher. In this post, we use WinCC Advanced Version 15.1 (TIA Portal V15.1) on Windows 10 Pro 64-bits (Version 1903) operating system.
      • For PLC device: Step7 Micro/WIN V4.0 SP9 on Windows 10 Pro 64-bits Version 1903.
  • The Hardware:

Could be helpful for you:

Config the connection parameters on the software

On S7-200 PLC Software – Step7 MicroWIN V4.0 SP9

To config on Step7 MicroWIN V4.0 SP9 for connect ktp700 basic hmi and s7-200 PLC please follow the steps:

  • Step 1: Click “System block” -> “Communication Ports”.
  • Step 2: Set the parameter: PLC Address: 2; Highest Address: 2; Baud rate: 187.5 kbps … See all in the picture below.ktp700 basic hmi and s7-200 communication 365evn
  • Step 3: Compile the project and download it to the PLC device. 

On KTP700 Basic DP HMI Software – WinCC Advanced V15.1

  • Step 1: Create a project and select KTP700 Basic DP. I used HMI Code: 6AV2 123-2GA03-0AX0.
  • Step 2: On “Project tree”, click “HMI [KTP700 Basis DP] -> “Connection”.
  • Step 3: Create an HMI connection to S7-200 PLC. The communication driver is “SIMATIC S7 200”.
  • Step 4: Set the parameters for connecting ktp700 basic hmi and s7-200
      • HMI device: Type: Simatic; Baud rate: 187500; Address: 1; Access point: S7ONLINE.
      • PLC: Address: 2connect ktp700 basic hmi s7-200
  • Step 5: Compile the project and download it to the HMI device. With KTP700 Basic you can download the project to the device by using a PROFIBUS/MPI cable or USB Disk. On our blog we guided both methods, you can refer to it.

Previous posts:

The cable for connection KTP700 Basic DP HMI To S7 200 PLC 

Check the HMI device serial interface, 9-pin sub-D socket, female as below:

ktp700 basic communication portFinal, we use the connection diagram to make the cable for communication ktp700 basic hmi and s7-200 PLC:

  • Pin no 3 of the HMI port to  pin no 3 of the PLC port (Data signal B+)
  • No 8 of the HMI port to  pin no 8 of the PLC port (Data signal A-)
  • Pin no 5 of the HMI port to  pin no 5 of the PLC port (GND 5V, floating)

Enjoy the result. Now, you can connect, control the S7 200 PLC with KTP700 Basic DP.

If you have any questions about: “Simatic KTP700 Basic HMI and S7-200 PLC Communication Use RS485 Interface” please comment below.

You can refer more about #hmi to plc

Good luck!
-365EVN; Refer: Siemens.com

 