Siemens Smart Line HMI IE V4 includes the SMART IE 700 (7-inch) / 1000 (10-inch) series. In this article, 365EVN guides you to transfer/download program to Smart Line HMI IE V4 from a USB Flash Drive.
Preparing For Download Program To Smart Line HMI IE V4
To transfer the program to Siemens Smart Line HMI IE V4 from a USB Flash drive, we use the hardware and software as below:
- Siemens Smart 700 IE V4 FW V4.0.2 – 6AV6648-0DC11-3AX0. On the 365evn shop, you can find it here at a low price.
- WinCC Flexible SMART V5 English (Patch) on Windows 11 x64. However, you can download and use the original version (Chinese language) with the same functions and menu locations.

- USB Flash Drive
Transfer Program To Smart HMI IE V4 Use USB Flash
Follow the steps to download program to Smart Line HMI V4 from a USB Flash drive.
Step 1 – Create a new project with WinCC Flexible SMART V5 English
- Open WinCC Flexible SMART V5. Click on the menu “Project” -> “New…“
- Then, select the device (Smart 700 IE V4) and the firmware version of device (V4.0.2.0)
- Click “OK” and go to the main screen of the SMART Line HMI programming software.
- However, if you already have a project file, you can skip this step and open it.

Step 2 – Transfer Program from WinCC Flexible SMART V5 to USB
- First, click on the menu “Project” -> “Compiler” -> “Compile” to check any issues.
- Put the USB Flash drive into the PC, and the file system of the device is FAT32.
- Then, click “Project” -> “Download to device…“, and change the setting:
- Mode: Export for USB stick
- Drive: Select your USB drive
- Alias: Option (Ex: Smart_700_IE_V4)
- Tick (or untick): Overwrite user administration data and Overwrite recipe data records

- Then, click “Download” button to transfer the program from WinCC Flexible SMART V5 to USB drive.
- Finally, open the USB drive and check. We have a new folder “SIMATIC.HMI” that contains the program data.
Step 3 – Download Program To Smart Line HMI From USB Drive
- Put the USB Flash drive into the Smart Line HMI IE V4. Turn on the power.
- Then, go to the system menu, touch on “Control panel“-> “Service & Commissioning” -> “Project” -> “Next“, select the USB drive and project file.

- Check the settings before transfer.
- Finally, press “Start” and download program to Smart Line HMI IE V4.

- Waiting for the process to complete and enjoy the new program.
Another way: Download Program To Smart Line HMI IE V4 through Ethernet Cable
Download Program to HMI Smart Line V4 Use USB Drive – Video Guide
If you find this content valuable, please rate it (click the button above), share it with your friends or invite me for a coffee by clicking the button below.